FANUC Alarm PAIN-483 — PAUS Pump 2 IN high pressure fault
FANUC PAIN-483 (“PAUS Pump 2 IN high pressure fault”): Pump #2 inlet pressure has been above the high fault limit for a user configurable period of time. First check: Make sure the high pressure fault limit is appropriate.
Updated 2026-09-17 · LogrobotLM reference
Description
Pump #2 inlet pressure has been above the high fault limit for a user configurable period of time. This condition is usually caused by one or more of the following: 1. The high pressure fault limit is set too low. 2. The high pressure sensitivity is set too short. 3. The supply pressure is set too high. 4. The hardener inlet transducer has failed. 5. The inlet regulator has failed.
Remedy
Make sure the high pressure fault limit is appropriate. Make sure the high pressure sensitivity is appropriate. Make sure the supply pressure is appropriate. Check the hardener inlet transducer as follows: Through the Analog I/O menu verify the transducer is spanning from near 200 cnts (0 psi) to 600+ cnts (50-80 psi) during a color change cycle. Check the hardener inlet regulator as follows: Through the Analog I/O menu verify the command 200-1000 cnts (0-100 psi) spanning by verifying the output psi at the transducer test port.