FANUC Alarm PAIN-513 — WARN %sMin. output has flow > setpoint
Description
With a minimum control output the flow rate was measured to be higher than the setpoint (requested flow). The Max. control out (ms) parameter effects the sensitivity of this alarm. This may be d by a leaking or broken air line between the flow sensor and the applicator. The I/P transducer may be stuck open. The air booster may be stuck open or leaking. This may be d by a faulty air flow sensor (reading more flow than there really is). Note, AccuAir temporarily automatically changes to Open Loop when this alarm occurs.
Remedy · Remède
Check and repair the various air lines. Check and repair the air booster. Check and repair the I/P transducer. Possibly increase the Max. control out (ms) parameter.
Related codes / Codes liés
Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. · Informations indicatives issues du terrain — le manuel du constructeur et ses procédures de sécurité font foi. Ne shuntez jamais un organe de sécurité ; consignez (LOTO) avant toute intervention physique.