FANUC Alarm PNT2-746 — %sPump 1 totals differ > tolerance
Description
The actual total flow out of pump #1 as measured by the fluid flow meter has a value that is different than the commanded total flow. This difference is larger than the total flow tolerance.
Remedy · Remède
Do a fluid flow test on pump #1 with a beaker and verify that the beaker amount matches the pump #1 size (cc/rev). Verify that the correct KFT factor has been entered for the fluid flow meter per the manufacturers specification. Check the operation of the inlet regulator to verify that no (blow by) is occurring across the pump. Verify that pump #1 does not have excessive wear.
Related codes / Codes liés
Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. · Informations indicatives issues du terrain — le manuel du constructeur et ses procédures de sécurité font foi. Ne shuntez jamais un organe de sécurité ; consignez (LOTO) avant toute intervention physique.