FANUC Alarm SRVO-076 — SERVO Tip Stick Detection

Manufacturer wording — SERVO Tip Stick Detection(G:%d A:%d)
The manual prints placeholders; your controller fills them in with the real group, axis or number.

FANUC SRVO-076 (“SERVO Tip Stick Detection”): The servo software detected a disturbance torque that was too high when motion starts, and tripped a Tip stick detection alarm. First check: Reset the robot by using the teach pendant reset and JOG the robot away from any obstruction.

Updated 2026-09-17 · LogrobotLM reference

Description

The servo software detected a disturbance torque that was too high when motion starts, and tripped a Tip stick detection alarm.

Remedy

Reset the robot by using the teach pendant reset and JOG the robot away from any obstruction. If no tip stick detection or collision, the load on the robot may exceed the specification. Check input power to the servo amplifier. It should be greater than 170 VAC phase-to-phase. Also check the voltage between U-V, V-W, and U-W. Each should measure the same (~210VAC).