FANUC Alarm SYST-134 — WARN Max. freq. exceeded ch.: %d
Description
A frequency input connected to one of the HDI inputs momentarily or for an extended time had a frequency exceeding the setting for the maximum. The channel or input number is indicated in the alarm text.
Remedy · Remède
Reduce or eliminate the noise on the signal with additional grounding or shielding. If the frequency dip switch setting on the HDI Pulse Module is for the low range (640 Hz) and normal input frequencies will be above this, change the settings. Change the dip switch setting to the high range (1000 Hz) and the system variable $FQINT_SETUP[n].$FREQ_MAX_AL to 1020. If the frequency dip switch setting on the HDI Pulse Module is for the high range (1000 Hz) and normal input frequencies will always be below the low range change the setting to the low range. If the device providing the frequency (a flow meter for example) is providing frequencies above 1000 Hz, either change settings on the meter or change the type of meter so that the frequency provided is reduced. To disable this alarm, change the setting of the system variable
Related codes / Codes liés
Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. · Informations indicatives issues du terrain — le manuel du constructeur et ses procédures de sécurité font foi. Ne shuntez jamais un organe de sécurité ; consignez (LOTO) avant toute intervention physique.