ABB Error 20253 — External device temperature high DRV1
ErrorABB 20253 (“External device temperature high DRV1”): External device temperature high DRV1: the temperature supervision of the DRV1 external axis channel reports overheating. Likely part: Axe externe / Sonde thermique DRV1 (axis external / thermal sensor DRV1).
Updated 2026-10-22 · LogrobotLM reference
What it means
External device temperature high DRV1: the temperature supervision of the DRV1 external axis channel reports overheating. Also triggers when no external equipment is connected.
What to check
- Check the presence and condition of the termination plug on the external axis connector (a missing termination simulates an open sensor).
- Measure the external axis PTC chain.
- Check the cabinet ventilation and ambient temperature.
- Note: Same thermal supervision logic as 39467 (drive unit) but on the external equipment side.
Part to check / replace
ABB 20253 points to the hardware below — start here before ordering.
Tap a part for every code that points to it — and verify the exact variant for your controller before ordering.
Related codes
Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. How this reference is built →