ABB Error 71367 — No communication with I/O unit
ErrorABB 71367 (“No communication with I/O unit”): No communication with I/O unit: no communication could be established with the I/O unit at start-up. Likely part: Unité d'E/S DeviceNet / Alimentation 24 V (Unité d'E/S DeviceNet / Alimentation 24 V).
Updated 2026-10-22 · LogrobotLM reference
What it means
No communication with I/O unit: no communication could be established with the I/O unit at start-up. Often accompanied by 71424 (bus off).
What to check
- Check the DeviceNet power supply: 24 VDC, pin 1 = 0 V, pin 5 = +24 V.
- Check the termination resistors (121 ohms between pins 2 and 4): without termination, the bus does not start.
- Check cables, connectors and network length/topology.
- Replace the faulty I/O unit.
- Adjust the Unit Trustlevel (0-3) if the unit may legitimately be absent.
- Note: Complements 71301 (DeviceNet bus communication fault), already listed. Former equivalent: "512 ERREUR CARTE D'E/S" (S2/S3).