FANUC Alarm PNT1-542 — %s abort, can fill timeout
Description
The canister position counts did not reach the fill counts before the Color Change Timeout expired. If this occurs during a Scale Calibration, then the can was not filled before the Scale Cal Step Time expired. This condition can exist if no paint has entered the can, or a loss of canister position feedback from the linear potentiometer. The Color Change Timeout needs to be increased. The Full Can counts have not been properly calculated.
Remedy · Remède
Establish the cause of the timeout. Verify the canister position feedback is operating properly. Feedback can be verified by checking the analog input (AIN[1, DISP]). Check the paint supply system. Check the color change valve operation. Check the color valve, if it is a color change fault or the dock solvent if this occurs during a scale calibration. Increase the Color Change Timeout. If the gun has been changed then a scale calibration might be required. Reset, and attempt to continue if this occur during automatic mode. If the robot is stuck in the docking station then switch to manual mode and run a de-dock move to move the robot to Home. If this alarm occurs during a scale calibration then increase the Scale Cal Step Time (40 seconds by default). It could require more time depending on the material used to scale calibrate.
Related codes / Codes liés
Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. · Informations indicatives issues du terrain — le manuel du constructeur et ses procédures de sécurité font foi. Ne shuntez jamais un organe de sécurité ; consignez (LOTO) avant toute intervention physique.