FANUC Alarm PNT1-565 — Lower output did not lower flow
Manufacturer wording — %sLower output did not lower flow
The manual prints placeholders; your controller fills them in with the real group, axis or number.
FANUC PNT1-565 (“Lower output did not lower flow”): As Accuflow steps down through the 10 points in the calibration table, it expects a lower flow for each decrease in the commanded flow value. First check: Perform the following:
Updated 2026-09-17 · LogrobotLM reference
Description
As Accuflow steps down through the 10 points in the calibration table, it expects a lower flow for each decrease in the commanded flow value. In this case, the flow did not decrease. This can be caused by low or pulsing fluid pressure, insufficient exhaust, or no quick exhaust on the fluid pilot air.
Remedy
Perform the following: