FANUC Alarm PRIO-022 — SYST Too much I/O data on I/O link

Error
Hardware
I/O Link and process I/O
Controllers
R-J3iB / R-30iA
FANUC class
SYSTEM

FANUC PRIO-022 (“SYST Too much I/O data on I/O link”): The devices connected to the I/O Link exceed the I/O link capacity. First check: Disconnect some devices.

Updated 2026-10-22 · LogrobotLM reference

Description

The devices connected to the I/O Link exceed the I/O link capacity. A total of 64 bytes of data each are available for input and output devices connected to the I/O link. Process I/O boards typically use 16 bytes of input and 16 bytes of output each. Digital modules generally use one byte for each 8 ports. Analog modules generally use two bytes per port

Remedy

Disconnect some devices.

Field diagnosis

The total data of the connected modules exceeds the bus capacity (64 bytes of input and 64 of output; a process board typically uses 16 and 16).

What to check

  • Remove modules or redistribute them onto a second bus.
  • Note: Count the bytes before adding an analog module: two bytes per channel.

Related codes