FANUC Alarm SRVO-156 — SERVO IPMAL alarm

Error
Hardware
servo amplifier
Controllers
R-J3iB / R-30iA / R-30iB
FANUC class
SERVO

Manufacturer wording — SERVO IPMAL alarm (G:%d A:%d)
The manual prints placeholders; your controller fills them in with the real group, axis or number.

FANUC SRVO-156 (“SERVO IPMAL alarm”): The IPM module has trouble. First check: Replace the IPM module.

Updated 2026-10-22 · LogrobotLM reference

Description

The IPM module has trouble.

Remedy

Replace the IPM module. Refer to the maintenance manual for details.

Field diagnosis

Abnormally high current detected by the intelligent power module of the amplifier.

What to check

  • Same procedure as SRVO-045: isolate the cable and motor of the axis (brake disconnected to prevent the axis from falling), test, measure the insulation, replace the faulty item.
  • Note: A recurring IPMAL on a single axis after a cell washdown indicates water ingress into the motor.

Related codes

Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. How this reference is built →