FANUC Alarm PNT1-703 — Failed to reach setpoint

Manufacturer wording — %sFailed to reach setpoint
The manual prints placeholders; your controller fills them in with the real group, axis or number.

FANUC PNT1-703 (“Failed to reach setpoint”): The turbine speed failed to come within the Tolerance Band setting within the time setting of Min. First check: N/A

Updated 2026-09-17 · LogrobotLM reference

Description

The turbine speed failed to come within the Tolerance Band setting within the time setting of Min. set point reached (ms) value. This can be caused by noise in the speed sensor signals, low air supply pressure or other failures. This may occur with the alarm Max. output has speed < setpoint. If the Max. output has speed < setpoint alarm is also in the alarm log follow the remedies for that alarm. Examine the displayed turbine speed and evaluate if it is bouncing a lot. If so decrease the PID gains. Possibly increase the Tolerance Band parameter by about 30… 50%, for example from 1.8… 2.3%. Increase the Min. set point reached value by about 30… 50%.