FANUC Alarm SRVO-134 — SERVO DCLVAL(PSM) alarm

Error
Hardware
servo amplifier
Controllers
R-J3iB / R-30iA / R-30iB
FANUC class
SERVO

Manufacturer wording — SERVO DCLVAL(PSM) alarm (G:%d A:%d)
The manual prints placeholders; your controller fills them in with the real group, axis or number.

FANUC SRVO-134 (“SERVO DCLVAL(PSM) alarm”): The back-up charge circuit for the amplifier has trouble. First check: Check the cables and connections between the amplifier (CN1) and the MCC. Likely part: E-stop unit (E-stop unit).

Updated 2026-10-22 · LogrobotLM reference

Description

The back-up charge circuit for the amplifier has trouble.

Remedy

Check the cables and connections between the amplifier (CN1) and the MCC. Check the fuse (F1,F3) in the transformer. If using a B-cabinet, replace the EMG control printed circuit board.

Field diagnosis

The DC voltage of the power supply module main circuit is too low: mains micro-outage, missing phase or weak supply network.

What to check

  • Look for a micro-outage in the workshop logs, measure each phase at the module input, check the transformer tap.
  • On R-30iB, lighten the program if the code only appears at high accelerations.
  • Note: A lost phase gives DCLVAL with the robot moving and nothing at standstill.

Part to check / replace

FANUC SRVO-134 points to the hardware below — start here before ordering.

Tap a part for every code that points to it — and verify the exact variant for your controller before ordering.

Related codes

Same hardware involved