FANUC Alarm PNT1-591 — Cal. time out at max. flow

Manufacturer wording — %sCal. time out at max. flow
The manual prints placeholders; your controller fills them in with the real group, axis or number.

FANUC PNT1-591 (“Cal. time out at max. flow”): Accuflow timed out trying to reach the maximum flow rate. First check: Decrease the gain modifier used for the color, if possible. Likely part: Fluid regulator (Fluid regulator).

Updated 2026-09-17 · LogrobotLM reference

Description

Accuflow timed out trying to reach the maximum flow rate. Possible causes are:

Remedy

Decrease the gain modifier used for the color, if possible. Then, retry the calibration. Check and change the transducer if necessary, replace the fluid regulator, or service the surge suppression system on the fluid supply pump. The calibration timeout parameter can also be increased.

Part to check / replace

FANUC PNT1-591 points to the hardware below — start here before ordering.

Tap a part for every code that points to it — and verify the exact variant for your controller before ordering.

Related codes

Same hardware involved

Indicative field information — the robot manufacturer's manual and safety procedures always prevail. Never bypass a safety device; apply lockout/tagout (LOTO) before any physical intervention. How this reference is built →