FANUC Alarm PAIN-584 — PAUS …0 res flow rate T.O.

Manufacturer wording — PAUS %s0 res flow rate T.O.
The manual prints placeholders; your controller fills them in with the real group, axis or number.

FANUC PAIN-584 (“PAUS …0 res flow rate T.O.”): All of the conditions were set for resin fluid to be flowing and a zero flow rate was measured. First check: Check that the gun is properly triggering. Likely part: Fluid flow meter (Fluid flow meter).

Updated 2026-09-17 · LogrobotLM reference

Description

All of the conditions were set for resin fluid to be flowing and a zero flow rate was measured. This may be caused by: a broken applicator trigger, a loss of resin fluid supply pressure, a broken flow meter, a broken cable (to the flow meter), or a Zero fluid flow timeout value that is too short. Note, Accuchop automatically faults the robot when this alarm occurs.

Remedy

Check that the gun is properly triggering. If fluid was observed to be flowing, check and possibly replace the fluid flow meter. Possibly increase the Zero flow timeout parameter (by about 25%).

Part to check / replace