FANUC SRVO-004 (“SERVO Fence open”): On the terminal block TBOP4 of the panel board, no connection is made between 5 (EAS1) and 6 (EAS11) or between 7 (EAS2) and 8 (EAS21). First check: 1. If a safety fence is connected, close the door. Likely part: Panel board (Operator panel board) +1 more.

Updated 2026-10-22 · LogrobotLM reference

Description

On the terminal block TBOP4 of the panel board, no connection is made between 5 (EAS1) and 6 (EAS11) or between 7 (EAS2) and 8 (EAS21). If a safety fence is connected between 5 (EAS1) and 6 (EAS11) or between 7 (EAS2) and 8 (EAS21), the door of the safety fence is open.

Remedy

1. If a safety fence is connected, close the door. 2. Check the switch and cable connected to 5 (EAS1) and 6 (EAS11) or 7 (EAS2) and 8 (EAS21). 3. When this signal is not used, make a connection between 5 (EAS1) and 6 (EAS11) or between 7 (EAS2) and 8 (EAS21). 4. If SRVO-004 (Fence open), SRVO-007 (External emergency stops), SRVO-213 (Fuse Blown (Panel PCB)), and SRVO-280 (SVOFF input) occur simultaneously, it is likely that FUSE1 on the panel board has blown. Check the fuse. If it has blown, remove the cause, then replace the fuse. Else, check the external voltage on EXT24V and EXT0V (TBOP6). If external 24V and 0V is not used check the jumper pins between EXT24V and INT24V, EXT0V and INT 0V (TBOP6). 5. If the problem still exists, replace the panel board.

Field diagnosis

In AUTO mode, the fence circuit connected to the dual inputs EAS1/EAS11 and EAS2/EAS21 is open.

What to check

  • Close the fence door after checking that nobody is inside the cell, then reset.
  • Otherwise check the switches and cables connected to both EAS channels on the emergency stop board terminal block; without a fence, the jumpers must be in place.
  • Note: A single open EAS channel gives SRVO-266/267 (chain), not SRVO-004: the code distinguishes an open door from an out-of-sync channel.